The National Fire Chiefs Council (NFCC) guidance for fire and rescue services on grid-scale battery energy storage systems (BESS) is the working reference that UK planning authorities and fire services lean on when a large battery site is proposed. It is guidance rather than law, but in practice it shapes site layout, separation distances and emergency planning for lithium-based BESS in the UK.
Published by: National Fire Chiefs Council (NFCC)
Current version: approved for publication in December 2025 and widely reported from February 2026; replaces the 2023 version
Status: informative guidance, not mandatory
Scope: open-air BESS of 1 MWh or more using lithium chemistries. Domestic systems (covered by PAS 63100:2024) and mobile or temporary deployments are excluded.
Related standards: NFPA 855, UL 9540A, UL 9540
Status and Who It Applies To
The NFCC states that the document does not constitute formal legal advice and is not a mandatory set of recommendations for local planning authorities. Fire and rescue services are not statutory consultees on BESS planning applications, although the guidance treats early engagement with them as good practice. Developers and operators remain responsible for safe design and operation. One industry commentary describes the guidance as the de facto standard, because planning authorities and fire services apply it in practice.
Key Points for Designers
- Risk management: operators are expected to run a risk assessment early and share an outline battery safety management plan and emergency response plan with the local fire and rescue service, covering alerting, site plans, warning systems, hazards and emergency isolator locations.
- Separation: an initial minimum of 30 m between cabinets (and transformers or switchgear) and occupied buildings, before mitigation such as blast walls. A trade report on the update puts the previous figure at 25 m. Spacing between cabinets can be reduced to 0.914 m (3 ft) only where UL 9540A testing shows no propagation, and vertical stacking is not supported.
- Vegetation, water and access: combustible vegetation kept at least 3 m from cabinets; hydrant flow of at least 25 L/s, or a static supply sized for about 120 minutes (roughly 180,000 L) placed at least 10 m from cabinets; vehicle access dimensions referenced to Approved Document B.
- Explosion protection and detection: deflagration venting or protection to recognised standards (the guidance cites BS EN 16009, BS EN 14373, BS EN 14797, NFPA 68 and NFPA 69), gas detection that shuts the system down and starts ventilation, and an aim of keeping the atmosphere below 25% of the lower explosive limit.
- Site information: sensitive receptors within 1 km shown on site plans, and signage showing the hazards, the technology, any suppression system and a 24/7 emergency contact.
- Recovery: plans for re-ignition risk, de-energising the system, and disposal of damaged equipment and contaminated fire water.
Background: Why It Was Revised
The NFCC says the update reflects new research, national and international standards, case studies and changing battery technology, and that it aims to keep fire service requirements proportionate to the risk without placing an undue burden on developers. The draft was consulted on in 2024. The Fire Protection Association’s report on the update also points to inconsistent approaches between fire and rescue services as a driver, and commentators link the 3 ft spacing option to test evidence from UL 9540A and to alignment with NFPA 855, which uses the same figure.
Points Still Open
One industry commentary lists questions the guidance leaves unresolved, including how its requirement for active ventilation sits alongside NFPA 855, which allows deflagration panels, whether fire prevention plans apply to BESS under environmental permitting, and how much detail the emergency response plan must contain. Treat these as the commentator’s reading rather than settled positions.
Disclaimer: This is not a definitive guide, just an indication and it is important that you always go back to the source for legislation.
References
- Grid scale energy storage system planning: Guidance for fire and rescue services, NFCC
- Fire chiefs update BESS guidance, Fire Protection Association
- NFCC issues updated BESS fire safety guidance, Solar Power Portal
- NFCC BESS guidance 2026: what is confirmed, what is open for UK EPCs, Reslink
See also: NFPA 855, UL 9540A, UL 9540, Propagation Mitigation