PAS 63100:2024

PAS 63100:2024 has been written to help installers manage the fire related hazards associated with Battery Energy Storage Systems (BESS) [3]. 

Specifies requirements for fire safety in the installation of small BESS units in domestic dwellings [1]:

  • physical requirements for battery units
  • battery management
  • power conversion equipment
  • fault management and fail-to-safe operation of all control and monitoring functions
  • installation location in respect of
    • safety and external influences that affect fire safety
    • protection against fire

SolarKinetics note [2] that batteries should not be installed in any of the following locations:

  • Rooms intended for sleeping.
  • Routes used as a means of escape that are not defined as protected escape routes, including landings, staircases, and corridors.
  • Corridors, shafts, stairs, or lobbies of protected escape routes.
  • Firefighting lobbies, shafts, or staircases.
  • Storage cupboards, enclosures, or spaces opening into rooms intended for sleeping.
  • Outdoors (ground-mounted or wall-mounted in a suitable enclosure) within 1m of escape routes, doors, windows, or ventilation ports.
  • Voids, roof spaces or lofts.
  • Within 2m of stored flammable materials and fuel storage tanks or cylinders.
  • Cellars or basements that have no access to the outside of the building.

References

  1. PAS 63100:2024 Electrical installations. Protection against fire of battery energy storage systems for use in dwellings. Specification, bsi
  2. New Fire Safety Standard for Battery Storage, SolarKinetics
  3. PAS 63100 – Protection Against Fire of Battery Energy Storage Systems, bsi

See also: GB/T 36276-2023